BIIC-Tech is a leading measurement company in China now,
dedicated to high-end analytical measuring instruments
DTZY47-M Three-Phase Smart Meter for commercial/industrial applications
Specifications
| Accuracy | Active Class B; Reactive Class 2 |
| Reference Voltage | 3×220/380V |
| Frequency | 50Hz |
| Operating Voltage | 0.9Un to 1.1Un |
| Basic Current | 5A |
| Rated Max Current | 60A |
| Power Consumption | ≤1.5W |
| Operating Humidity | 45%–75% RH |
| Operating Temperature | -25°C to +55°C |
| Design Life | 16 years |
| Dimensions | 290mm (H) × 170mm (W) × 85mm (D) |
| Net Weight | 2.2kg |
Features
-
Metering
-
Demand Measurement
- Tracks bidirectional max demand, TOU demand with timestamps.
- Sliding window method (default: 15-min cycle, 1-min interval).
- Manual demand reset supported; stores last 12 billing cycles’
-
Real-Time Monitoring
- Measures voltage, current, power, power factor per phase.
- Threshold alarms for voltage/current/power factor excursions.
-
Clock
Temperature-compensated clock with 1Hz output; automatic leap-year adjustment.
-
Tariff & Time Zones
- 2 programmable time-zone/day-schedule tables (auto-switch).
- 14 time segments/day (min. 15-min interval); 12 tariff rates.
-
Event Logging
- Records: Programming (10 most recent), demand resets, time calibrations, phase loss (voltage/current), voltage reversal, cover opening, meter resets, overloads, power failures, remote trip/close commands.
- Permanent log for meter reset events.
-
Data Freeze
Instant freeze (last 3), hourly freeze (last 254), daily freeze (last 62), monthly freeze (last 12), billing-day freeze (last 12), minute freeze (300 days at 15-min intervals).
Power-Off Data Read
Wake via button or infrared ("68 11 04" command); non-contact wake disabled after 7 days without power.
-
Prepayment Control
- Remote top-up via public network/carrier.
- Alerts when balance ≤ threshold; disconnects load if overdrawn.
- Restores supply after balance update.
- Supports direct remote close/allow close commands.
-
Forced Power-On
- "Force Power-On" mode blocks all trips until deactivated.
- Restores supply without changing meter state.